Quad — 20 ft standard DC block

Four DC blocks in a 2×2 cluster with one PCS & MV skid — the densest single section

Overview

Four DC blocks arranged in a 2×2 cluster with one PCS & MV skid below.

PCS & MV skid
Quad — 2×2 cluster, single skid below
ParameterValue
DC blocks4 × 20 ft (2×2 cluster)
PCS & MV skid1 × 40 ft
Section width12.3 m (40.4 ft)

Energy capacity

At 2h the four blocks exceed a single skid’s conversion capacity, so the solver automatically uses Quad Split with two skids instead.

DC blockBESS section (4 blocks)Duration
6.25 MWh25 MWh / 6.25 MW4h

Clearance and spacing defaults

Service clearance and spacing used by default. All values are adjustable in BESSLayout.

SettingDefault
DC block door side3.5 m (11.5 ft)
DC block cable end2 m (6.6 ft)
PCS & MV skid3 m (9.8 ft) all sides
Fire separation (between DC blocks of different sections)5 m (16.4 ft)

Cable layout

All four DC blocks cable down to the single PCS & MV skid. At 40 ft the skid has two PCS sections — each section serves one column.

Single BESS section footprint

Land area at default clearance. Door clearance above, skid clearance below, cable-end clearance on each side.

Doors facing outward

Skid below the 2×2 cluster, top-row doors facing up

286 m²(3,076 ft²)
16.3 × 17.5 m
53.5 × 57.5 ft
Land useValue
Footprint16.3 × 17.5 m (53.5 × 57.5 ft)
Total area286 m² (3,076 ft²)

Multiple BESS sections footprint

Land area for four sections, in a row and in a 2 × 2 grid, at the default spacing.

Clearance
4 × 1 grid

4 sections · 16 DC blocks

1196 m²(12,869 ft²)
68.3 × 17.5 m
224.0 × 57.5 ft
2 × 2 grid

4 sections · 16 DC blocks

1060 m²(11,413 ft²)
33.6 × 31.5 m
110.3 × 103.4 ft