BESS section configurations

How BESSLayout arranges DC blocks and PCS skids into sections.

A BESS sectionis a group of one, two, or four DC blocks and the PCS & MV skid that serves them.

How many DC blocks share a skid depends on duration. At shorter durations the power demand is higher, so each skid serves fewer blocks. The default pairing for each configuration is shown below. Either skid size (20 ft or 40 ft) works with any configuration — see Supported equipment for ratings, or set a specific size with the PCS config card.

Solo

Standalone DC blocks, never joined to a neighbor. Both orientations put one block on a 20 ft skid at either duration — the fallback tier for thin strips and leftover corners. Solo Centered is the exception: one centered skid feeds a block on each long side, so it sizes like a twin (40 ft @2h / 20 ft @4h).

Twin

Two DC blocks per skid: a 40 ft skid at 2h, a 20 ft at 4h. The mirror and compact arrangements pair two twins around a shared aisle — each pair keeps its own skid. The centered arrangements put both twins on one 40 ft skid instead, and a 40 ft skid carries four blocks only at 4h, so those two are 4h only.

Quad

Four DC blocks on one 40 ft skid — but only at 4h. At 2h those four blocks draw more power than a single skid can convert, so a Quad builds as Quad Split, with a skid on each DC row. The footprint stays available at both durations; only the skid count changes.

Auto vs. forcing a configuration

On Auto the solver keeps the densest valid section per zone, which is why an irregular site shows a mix: quads in the open field, twins in a narrower arm, a solo in a corner. Forcing a configuration pins every zone to one arrangement — the right call when your project standardizes on a section design, and a quick way to see what that standard costs in capacity.

Your DC block configuration filters the list — forcing Twin hides the quad family, forcing Solo leaves only single blocks — and duration gates the one-skid sections (the quads and the centered twins), as noted above. Diagrams are drawn at 4h.

Reading a layout

The pale grey end on each DC block is its cooling and cable end; it always faces the skid or the outside of the cluster, never another blind side. Doors sit on the long sides facing an aisle. If every block traces to a skid and every door to open space, you are reading the layout the way the solver built it.