Twin Long — 20 ft standard DC block

Two DC blocks joined on their blind long sides with a PCS & MV skid beside the cable ends

Overview

Two DC blocks joined on their blind long sides, doors facing outward both ways. One PCS & MV skid (20 ft or 40 ft) sits beside the cable ends.

PCS & MV skid
Twin Long — cable end facing the skid
ParameterValue
DC blocks2 × 20 ft
PCS & MV skids1 × 40 ft @2h · 20 ft @4h
Section size21.3 × 5.1 m (69.7 × 16.7 ft)

Energy capacity

Section energy and power rating for this configuration.

DC blockBESS section (2 blocks)Duration
6.25 MWh12.5 MWh / 6.25 MW2h
6.25 MWh12.5 MWh / 3.125 MW4h

Clearance and spacing defaults

Service clearance and spacing used by default. All values are adjustable in BESSLayout.

SettingDefault
DC block door side3.5 m (11.5 ft)
DC block cable end2 m (6.6 ft)
PCS & MV skid3 m (9.8 ft) all sides
DC block stacking gap0.2 m (0.7 ft)
Fire separation (between DC blocks of different sections)5 m (16.4 ft)

Cable layout

DC cables run from each block's cable end to the adjacent PCS & MV skid.

Single BESS section footprint

Land area at default clearance. When the cable end faces the skid, its clearance zone overlaps with the skid zone — no extra width on that side.

Cable end facing the skid

Cable-end clearance shared with skid zone

293 m²(3,152 ft²)
24.3 × 12.1 m
79.6 × 39.6 ft
Cable end facing outward

Cable-end clearance extends outward

317 m²(3,412 ft²)
26.3 × 12.1 m
86.1 × 39.6 ft
Land useCable inwardCable outward
Footprint24.3 × 12.1 m (79.6 × 39.6 ft)26.3 × 12.1 m (86.1 × 39.6 ft)
Total area293 m² (3,152 ft²)317 m² (3,412 ft²)

Multiple BESS sections footprint

Land area for four sections, in a row and in a 2 × 2 grid, at the default spacing.

Clearance
4 × 1 grid

4 sections · 8 DC blocks

1171 m²(12,609 ft²)
97.0 × 12.1 m
318.2 × 39.6 ft
2 × 2 grid

4 sections · 8 DC blocks

1074 m²(11,564 ft²)
48.5 × 22.2 m
159.1 × 72.7 ft