Twin Short Compact — 20 ft standard DC block

Four DC blocks in two end-to-end pairs, each pair with its own PCS & MV skid — the tightest twin arrangement on shallow sites

Overview

Four standard DC blocks in two end-to-end pairs, each pair with its own PCS & MV skid (20 ft or 40 ft). The sandwich: DC row, skid row, DC row.

PCS & MV skid
Twin Short Compact — doors facing the skid aisle
ParameterValue
DC blocks4 × 20 ft
PCS & MV skids2 × 20 ft / 40 ft
Section size12.3 × 14.3 m (40.4 × 47.0 ft)

Energy capacity

Section energy and power rating for this configuration.

DC blockBESS section (4 blocks)Duration
6.25 MWh25 MWh / 6.25 MW4h
6.25 MWh25 MWh / 12.5 MW2h
5.016 MWh20.064 MWh / 10.032 MW2h

Clearance and spacing defaults

Service clearance and spacing used by default. All values are adjustable in BESSLayout.

SettingDefault
DC block door side3.5 m (11.5 ft)
DC block cable end2 m (6.6 ft)
PCS & MV skid3 m (9.8 ft) all sides
DC block stacking gap0.2 m (0.7 ft)
Fire separation (between DC blocks of different sections)5 m (16.4 ft)

Cable layout

DC cables run from each DC block to its paired PCS & MV skid in the central row.

Single BESS section footprint

Land area at default clearance. When DC block doors face the skid, their service zones overlap — reducing total footprint.

Shared clearance

DC block service doors facing the skid

435 m²(4,681 ft²)
30.4 × 14.3 m
99.7 × 47.0 ft
Separate clearance

DC block service doors facing outward

617 m²(6,644 ft²)
30.4 × 20.3 m
99.7 × 66.6 ft
Land useSharedSeparate
Footprint30.4 × 14.3 m (99.7 × 47.0 ft)30.4 × 20.3 m (99.7 × 66.6 ft)
Total area435 m² (4,681 ft²)617 m² (6,644 ft²)

Multiple BESS sections footprint

Land area for four sections, in a row and in a 2 × 2 grid, at the default spacing.

Clearance
4 × 1 grid

4 sections · 16 DC blocks

1611 m²(17,339 ft²)
112.5 × 14.3 m
369.2 × 47.0 ft
2 × 2 grid

4 sections · 16 DC blocks

1943 m²(20,910 ft²)
57.8 × 33.6 m
189.5 × 110.3 ft